FindItForMe!

24 Hour Legionella testing by PCR

Quantification of Legionella in 24 hours using UKAS accredited real time PCR method

The standard method for the quantification of Legionella in water systems is a ‘culture method’ which is labour intensive and can take up to 12 days to generate a confirmed result.

ALcontrol is able to offer a UKAS accredited real-time assay for the quantification of Legionella in environmental samples using GeneExtract® for DNA extraction and purification and GeneDisc® Cycler for real-time PCR.

Benefits of PCR

·Treatment improved optimisation - Efficiency of biocide costs

·Crisis prevention - What’s the price of a crisis?

·Continual Monitoring- To enable effective decisions on treatment

Analytical process

·Filtration – through 0.45µm polycarbonate membrane

·DNA Extraction – lysis buffer, sonication and heating

·DNA Purification – to isolate DNA

·PCR analysis – sample mixed with enzymes to amplify DNA, fluorescence signal intensity is then measure

Technical Specifications

·Two Genediscs are available specific to detect either Legionella spp. or Legionella pneumophila

·Detection limit of 167 Genomic Units per litre

·Suitable for a range of matrices

- Up to 1 litre for Process waters

- 10g for Solid samples

- Up to 1 litre for Environmental waters

·Sensitivity – greater sensitivity than the culture method

·Practicality – high solid/turbid samples easier to analyse

Customer Focused

Our Customer Services Team works closely with clients and is always on hand to help.

·Testing within 24 hours

·A reported result turnaround time of 48 hours

·Tailored packages to meet specific requirements

·Free sample bottles supplied

·Electronic reporting formats including Internet or email

Frequently Asked Questions

How does the GeneExtract® detect only viable Legionella?

The 0.45µm polycarbonate membrane lets free DNA pass through the membrane and retains fully formed cells. Therefore only viableLegionella are retained on the membrane.

What is the difference between CFU and GU?
CFU is the measurement unit of the ability of a cell to form a colony. Treatment stressed cells maybe present but not grow using a culture method. GU is a measure of the total genetic material within the sample. In this case it is specific to Legionella.








Click here to find out more about ALcontrol Laboratories


Email  Send to a friend   Print  Printer friendly   Print  Link to this page
del.icio.us digg technorati cosmos blinklist reddit newsvine nowpublic stumbleUpon Add to diigo Add to LinkedIn Retweet this on Twitter Facebook



N.B. The information contained in this entry is provided by the above supplier, and does not necessarily reflect the views and opinions of the publisher



Home About Us Suubscribe Advertise Digital Editions Networking Your Account Contact Us
FHG  
Other Faversham House Websites include
FHG Media | ACR-News | HousewaresLive | web4water | DIY Week
RSS Feeds | All the latest articles All the latest articles | Latest Events Upcoming Events | Latest Jobs Latest jobs | Bookmarks Bookmarks